- •Theoretical data
- •Setting of protection functions of mp3c-05
- •General guidance
- •Work order
- •Measured indications and their measuring accuracy
- •Checking of maximal current protection (mcp)
- •Checking of maximal current protection (mcp) attention!
- •It’s not allowed to set parameters of mt3 less than 2.7 a.
- •Change of drawdown parameters of current protections of mp3c-
- •Check of maximal voltage protection (зНмах).
- •Parameters set of maximal voltage protection (зНмах).
- •Measuring of parameters of maximal voltage protection actuation (зНмах)
- •Checking of minimal voltage protection (3Hmin)
- •Setting of protection parameters of minimal voltage (3Hmin)
- •Changing of minimal voltage protection parameters actuation (3Hmin)
- •5. Contents of report
- •Laboratory work # 5
- •Laboratory work # 5
- •Theoretical information
- •AIlBointment of automated functions mp3c-5
- •General instructions
- •Work and functional block scheme аг1в, уров
- •Automatic reclosing of апв
- •Breaker failure protection device (уров)
- •Work order
- •The parameters and the accuracy of their measurement
- •Checking of апв.
- •Setting of parameters апв mp3c-05
Change of drawdown parameters of current protections of mp3c-
05.
Set on the checkout console voltage of 60 V on phases А, В, C. Increase smoothly current la on the console of minimal value of drawdown 1 CT MT3 (drawdown console 1 CT MT3 takes place after lightening of light-emitting diode D.l on the MP3C-05). Fix on display of MP3C-05 in the menu CHANGES current value of protection actuation ICP
Decrease
la until switching off of Dl. Fix on the MP3C-05 in the menu
MEASUREMENTS value of protection return current IB.
Set current Phase A to minimal value. Calculate the formula return
on current protection
Similar measurements are performed for the currents lb, Ic. These measurements and calculations should be tabulated into a table 2.
Table 2
№ |
Cascade MT3 |
Phase |
1у (А) |
1ср (А) |
1в (А) |
К HI |
8,. % |
1. |
MT31 |
A |
2,7 |
|
|
|
|
2. |
MT32 |
A |
2,8 |
|
|
|
|
3. |
MT33 |
A |
2,9 |
|
|
|
|
4. |
MT31 |
В |
2,7 |
|
|
|
|
5. |
MT32 |
В |
2,8 |
|
|
|
|
6. |
MT33 |
В |
2,9 |
|
|
|
|
7. |
MT31 |
С |
2,7 |
|
|
|
|
8. |
MT32 |
С |
2,8 |
|
|
|
|
9. |
MT33 |
С |
2,9 |
|
|
|
|
Compare KH], 8, with permissible values from table 1.
Check the operation of the functions assigned to the digital inputs:
S I AT BE MTZ1 on DV7;
STAT BE MTZ2 on DV7;
STAT BL MTZ3 on DV7.
To do this, select the row Diskret INPUTS, press ENTER, and then DV07 - INVERTED
Increase the current in any phase up to 3 A. Make sure that the emptying to all levels of MTZ block.
Check of maximal voltage protection (зНмах).
Parameters set of maximal voltage protection (зНмах).
Go to the menu of MP3C-05 device, select program module CONFIGURATION and set:
311 -Turn in.
Another types of protection are turn off.
Sequentially choose program modules 3H, SETTING and, relieve INPUTS, OUTPUTS COM, INDICATION and set:
SETTING:
MAX. VOLTAGE - 30,0 B;
RESTRAINTS:
RESTRAINTS UMAkc - 0,1 c;
CONTROL:
PROTECTION Umakc - TURN ON;
SETTING
OUTPUT COM:
P05 - ACTUATION UMakc~ TURN ON;
INDICATION:
СДИ4 - ACTUATION UMAkc - TURN ON;
Select in the program module SETTING row УВВ and push button INPUT.
Select row INDICATION and push button INPUT, set:
СДИ4- NORMAL;