- •Theoretical data
- •Setting of protection functions of mp3c-05
- •General guidance
- •Work order
- •Measured indications and their measuring accuracy
- •Checking of maximal current protection (mcp)
- •Checking of maximal current protection (mcp) attention!
- •It’s not allowed to set parameters of mt3 less than 2.7 a.
- •Change of drawdown parameters of current protections of mp3c-
- •Check of maximal voltage protection (зНмах).
- •Parameters set of maximal voltage protection (зНмах).
- •Measuring of parameters of maximal voltage protection actuation (зНмах)
- •Checking of minimal voltage protection (3Hmin)
- •Setting of protection parameters of minimal voltage (3Hmin)
- •Changing of minimal voltage protection parameters actuation (3Hmin)
- •5. Contents of report
- •Laboratory work # 5
- •Laboratory work # 5
- •Theoretical information
- •AIlBointment of automated functions mp3c-5
- •General instructions
- •Work and functional block scheme аг1в, уров
- •Automatic reclosing of апв
- •Breaker failure protection device (уров)
- •Work order
- •The parameters and the accuracy of their measurement
- •Checking of апв.
- •Setting of parameters апв mp3c-05
Measuring of parameters of maximal voltage protection actuation (зНмах)
Decrease
Ua until СД4
will be deactivated. Set on ЖКИ
of MP3C-05 in the menu MEASURING value - voltage of protection
return to initial state UB.
Calculate coefficient of return according to voltage value:
Analogical measurement must be made for voltage phase В & С. Measuring data and calculation write to 'Fable 3.
Table 3
№ n/ П |
Protect i о n type |
Voltage phase |
Uy (В) |
иСР (В) |
ив (В) |
Кт, |
4м % |
1. |
UMax |
А |
30 |
|
|
|
|
2. |
UMax |
А |
60 |
|
|
|
|
3. |
имах |
А |
100 |
|
|
|
|
4. |
UMax |
В |
30 |
|
|
|
|
5. |
UMax |
В |
60 |
|
|
|
|
6. |
UMax |
В |
100 |
|
|
|
|
7. |
имах |
С |
30 |
|
|
|
|
8. |
имах |
С |
60 |
|
|
|
|
9. |
имах |
С |
100 |
|
|
|
|
CompareKHU , Su with permissible values from table 1.
Checking of minimal voltage protection (3Hmin)
Setting of protection parameters of minimal voltage (3Hmin)
Enter the programming modules ЗН, НАСТРОЙКА, free used INPUTS, OUTPUTS of КОМ,INDICATION from previously given functions and set:
SETTINGS:
MIN VOLTAGE - 30 V;
RESTRANTS:
RESTRANT OF Umin - 0,1 s;
CONTROL:
PROTECTION Umin- TURN ON;
OUTPUTS OF КОМ :
P06 - СРАБ U min- TURN ON;
INDICATION:
СДИ5 - СРАБ U min - TURN ON;
Select in the programming module SETTING sring УВВ and press button ENTER.
Select string INDICATION, press button ENTER and set:
СДИ5-NORMAL;