- •Theoretical data
- •Setting of protection functions of mp3c-05
- •General guidance
- •Work order
- •Measured indications and their measuring accuracy
- •Checking of maximal current protection (mcp)
- •Checking of maximal current protection (mcp) attention!
- •It’s not allowed to set parameters of mt3 less than 2.7 a.
- •Change of drawdown parameters of current protections of mp3c-
- •Check of maximal voltage protection (зНмах).
- •Parameters set of maximal voltage protection (зНмах).
- •Measuring of parameters of maximal voltage protection actuation (зНмах)
- •Checking of minimal voltage protection (3Hmin)
- •Setting of protection parameters of minimal voltage (3Hmin)
- •Changing of minimal voltage protection parameters actuation (3Hmin)
- •5. Contents of report
- •Laboratory work # 5
- •Laboratory work # 5
- •Theoretical information
- •AIlBointment of automated functions mp3c-5
- •General instructions
- •Work and functional block scheme аг1в, уров
- •Automatic reclosing of апв
- •Breaker failure protection device (уров)
- •Work order
- •The parameters and the accuracy of their measurement
- •Checking of апв.
- •Setting of parameters апв mp3c-05
Changing of minimal voltage protection parameters actuation (3Hmin)
Work order of 3Hmin:
Actuation of 3Hmin happens when voltage on all 3 phases А, В, С becomes less than voltage installed.
Set on the console voltage of 20 V by phases В and С and 50 V by phase A. Smoothly decrease voltage Ua on the console till drawdown 3Hmin (drawdown control 3nmin is held at lightening of light-emitting diode D5 on the MP3C-05). Fix on the ЖКИ MP3C-05 in menu CHANGES value of voltage protection actuation Ucp. Calculate according to the formula accuracy of voltage protection actuation:
Set the voltage of 50 V on the console on phases В and C. Increase Ua till switching off of the LED D5. Fix on ЖКИ MP3C-05 in menu MEASUREMENTS value - voltage of reverse protection in initial state UB.
Calculate according to the formula coefficient of reverse voltage:
Make similar changes, changing voltages of phases В and C.
Check parameters of 3Hmin for restraints by voltage 60 V and 100 V by mentioned above principle.
Put measurements and calculation data into table 4.
Table
4
№
п/
П
Protectio
n type
Voltage
phase
Uy
(V)
Ucp
(V)
UB
(V)
К*,
s(!,
%
1
Знтт
А
30
2
Знтт
А
60
3
Знтт
А
100
4
Знтт
В
30
5
Знтт
В
60
6
Знтт
В
100
7
Знтт
С
30
8
Знтт
С
60
9
Знтт
С
100
Compare
Кни
,
Su
with allowable meanings from table 1
5. Contents of report
Cover page with laboratory work title.
Description of the process of diagnostics of MP3C-05 parameters.
Work results data table.
Conclusions.