Refer to the back of this manual for Factory Service and Technical Support contact information

6.4.4Battery Monitor

6.4.4.1Enable

This menu item enables the Supervisor to control the CXC’s battery monitor feature.

Battery Properties section must be completed to enable this feature.

6.4.4.2Load Type

This menu item enables the Supervisor to select the type of load on the system: constant power, current, or resistive. This is used for battery capacity calculations.

6.4.4.3Disconnect Voltage

The disconnect voltage should be set to the value of the LVD that will disconnect the battery from the load. The Battery Runtime algorithm uses this value to calculate the hours remaining during an AC outage.

6.4.4.4Reset Battery Monitor

The Battery Monitor should be reset when installing new or different batteries.

6.4.4.5Battery Properties (See 6.4.8)

The “Battery Properties” button at the bottom of the Battery Monitor window is a link to the Battery Properties window.

The return path (the menu structure) will remain intact; i.e., the user will return through the window where the Battery Properties button was tapped.

6.4.5Battery (Discharge) Test

The Battery Test (BT) is used to update the status of the battery capacity. It can be set to run automatically or can be initiated manually (via Mode Selection button). See 4.3.4 for more details.

6.4.5.1BT End Voltage

This menu item controls the end (or termination) voltage of the BT; +0.5V above Rectifier BT Voltage is recommended.

Rectifier BT Voltage (identical to 6.3.2.3 – a change in one alters the other)

This menu item enables the Supervisor to set the Rectifier BT Voltage to the desired value during the test (mode). This setting should have a minimum of LVD + 1V.

Rectifier BT Timeout (identical to 6.3.2.11 – a change in one alters the other)

This menu item controls the duration of the Battery Test.

6.4.5.2Auto-BT

Enable

This menu item enables the Supervisor to control the CXC’s Auto-BT feature.

Interval

This menu item enables the Supervisor to program the time, in days, between Auto Battery Tests.