Refer to the back of this manual for Factory Service and Technical Support contact information

6.9Hardware

This menu category consists of output relay configuration and testing. See also 6.5.3.1 for Overview.

6.9.1Configure Relays

This menu item will display a list of the normal state of all the existing output relays. A relay must be selected in order to configure the settings. See Figure 87 below.

From the pop-up menu, the Supervisor can configure the relay for email notification and/or SNMP dial out trap notification. The Supervisor can also toggle polarity; that is, specify if the relay is normally energized or normally de-energized.

Select from the pop-up menu

Select relay then tap

Configure Settings

Figure 87–Configure Relays window

6.9.2Test Relays

This menu item will display a list of the present state of all existing output relays. See Figure 88 below.

From this menu the Supervisor can toggle the state; that is, specify if the relay is presently energized or deenergized to verify its condition. Change of state will be temporary as all relays return to their default states after leaving this menu.

Discard changes and return to previous screen

Select menu item to test

Sliders and scroll bars are used for navigation

Tap Toggle State to test selected item

A message of warning will be displayed before allowing the toggling of an LVD relay

to enable the user to cancel the operation.

Figure 88–Test Relays window

6.9.3Test Modem (Web Interface only)

See 9.3.3.

0350046-J0 Rev C

Page 86 of 127