6.6.2Configure Signals

This menu item provides a link for the Supervisor to configure controller Signals (and Analog Inputs described above). The status of Digital Inputs and Rectifier Signals may also be viewed under this menu.

6.6.2.1Controller Signals

Select this heading from the pull-down menu to access/edit the list of Controller Signals (4.5) menu items such as load current and battery temperature (to enable sensors, see Figure 52).

Once a menu item is selected, tap the “Configure” button to produce another window and list of items4 to navigate and edit. See examples on the next page.

Definitions

Load Voltage — The discharge voltage. Load Current — The discharge current.

Battery Voltage — The charge or system voltage. Battery Current — The charge current.

AC Mains — The average rectifier input voltage. AC Correction appears when AC Mains is selected.

Total Rectifier Current — The sum of rectifier output currents.

Battery Temperature — The average of enabled sensors (if temperature sensors agree within 5%) or the peak value of enabled sensors (if temperature sensors do not agree within 5%). Battery Run Time — The estimated time remaining before LVD.

Battery Capacity — A battery’s estimated ability to store charge.

Battery Depth of Discharge — An estimate of the energy removed from a battery during a discharge.

Converter Load Voltage — The converter output voltage. Converter Load Current — The converter output current.

The table below summarizes the default controller signal equations:

Controller Signals

Signal Equations

Load Voltage

[V1]

Load Current

[I1]

Battery Voltage

[V2]

Battery Current

[Total Rectifier Current] – [Load Current]

Table D–Controller signal default definitions

6.6.2.2Analog Inputs

Select this heading from the pull-down menu to access/edit list of Analog Inputs menu items. See 6.6.1 for details.

6.6.2.3Digital Inputs

Select this heading from the pull-down menu to access a list of all the existing digital channels, see 6.5.3.3 for Alarms. The status of the channel, high or low, is displayed in the column next to the channel name.

6.6.2.4Rectifier Signals

Select this heading from the pull-down menu to access a list of all the existing rectifier signals. The status of the signal is displayed in the column next to the signal name.

4 “Signal Equation” or “Customize” does not appear for AC Mains or Battery related menu items.

0350046-J0 Rev C Page 64 of 127